and with reduced emission of corrosive gases,
single core without sheath, pvc insulated, with flexible conductor in red copper.unel
fs17-450 / 750v
conductor: red copper, flexible formation, class 5
insulation: pvc, r2 quality
functional characteristics
rated voltage uo / u: 450/750 v
maximum working temperature: 70 ° c
maximum short circuit temperature: 160 ° c
particular characteristics
good flow in pipes, good flexibility and resistance to abrasion, excellent peelability.
installation conditions
minimum installation temperature: 5 ° c
minimum recommended bending radius: 4 times the diameter of the cable
maximum recommended tensile stress: 5 kg per mm² of copper section
use and type of installation
in environments with a risk of fire. installation within exposed pipes o
built-in or similar closed systems. fixed installation within lighting fixtures or switching and control equipment; in this case i
cables are allowed for voltages up to 1000 v ac and 750 v to earth.
the section of 1 mm² is intended only for electrical circuits of lifts and
goods lifts or for internal connection of electrical panels for signaling e
command.
for installations at risk of fire, the maximum operating temperature must not exceed 55 ° c. not suitable for outdoor installation. (cei 20-40)
-> the price refers to the mt.
-> also sold by the meter.
- skein of 100 mt
- section 63mmq
- blue color
- imq quality mark